94 Parameters
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
189 Inverter control
189.01
Inverter operation
Enables inverter operation. Inverter connects to
grid only when it is enabled. When disabled,
inverter disconnects immediately from the AC
grid.
0
0 … 1
0 = Inverter disabled
1 = Inverter enabled
1 = 1
189.07
Night mode
Sets night mode.
Sleep
Monitor
Inverter stays powered up from AC grid during the
night time.
0
Sleep
Inverter is powered down during the night time.
The rise of the DC voltage or control unit
interaction wakes up the inverter from sleep.
1
189.20
Disconnection delay
Defines time limit for disconnection.
Active power must be less than disconnecting
level for this amount of time for the inverter to
disconnect.
30 min
0 … 180 min
1 = 1 min
189.21
Disconnection power
Defines power level for inverter to disconnect
from grid.
See also description in chapter
1%
0 … 10%
10 = 1%
189.30
Output DC protection
Enables output DC current monitoring and
protection.
1
0 … 1
1 = 1
189.33
DC protection limit
Sets allowed level of DC component in the
measured inverter current.
1 A
0 … 10 A
1 = 1 A /
100 = 1 A
189.38
DC protection limit slow
Sets allowed level of DC component in the
measured inverter current. This value is used in
slow detection.
0.25 A
0 … 10 A
1 = 1 A /
1000 = 1 A
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...