132 Dimension drawing
Required installation clearances
Make sure that:
• You obey the minimum installation clearances.
• There is sufficient cooling airflow.
• The cooling fans can be accessed for maintenance.
• The inverter labels can be read.
Recommendations:
• If it is possible, install several inverters in one row, not on top of each other.
• Leave as much space between several inverters as possible.
• Install inverters as low as possible.
• When you install inverters on top of each other, obey these minimum clearances:
min.
350 mm
(13.8 in.)
min.
350 mm
(13.8 in.)
min.
250 mm
(9.8 in.)
min.
500 mm
(19.7 in.)
min.
150 mm
(5.9 in.)
min.
520 mm
(20.5 in.)