Ambient Temperature
Section 7 Additional Installation Tips
1.
Use an EMC cable gland or regular plastic cable gland, remove the outer jacket
and connect the shield to the installation plate with a 360° metal cable clamp.
2.
Place the 24 V DC and communications cabling in one cable trunk/cable duct
and 230/380 V AC in another. If the cables need to be crossed, cross them at
90° only. Avoid combining the cabling for stronger 24 V DC outputs with
the communication cabling.
Ferrite cores that are snapped onto the shielded cabling may remove minor
disturbances. Large ferrite pieces that are snapped onto unshielded cabling and where
the wires go 2-4 times around the cores are approximately 5-25 times more efficient.
Ambient Temperature
The maximum ambient temperature for the operator panel is provided in the
specifications. The ambient temperature refers to the temperature in the device
cabinet which cools the operator panel’s electronics.
Operator
panel
Power
Power
Power
30 °C outside
Top
50 °C inside
Bottom
40 °C inside
Middle
45 °C inside
Airflow
Axial fan
120 x 120 mm
In most cases, the ambient temperature for the operator panel is significantly higher
than the device cabinet’s ambient temperature.
If the cabinet is tall and there are a number of heat-generating devices, the
temperature at the top of the cabinet is considerably higher than the temperature
increase that would be expected. All electronics are sensitive to heat. The lifespan of
38
3BSE069462-600 Rev D
Summary of Contents for PP882
Page 1: ...Compact Product Suite Panel 800 Version 6 PP882 Hardware and Installation ...
Page 2: ......
Page 3: ...Panel 800 Version 6 PP882 Hardware and Installation ...
Page 6: ...6 3BSE069462 600 Rev D ...
Page 16: ...Appearance of Air in Touch Screen Section 2 Safety Precautions 16 3BSE069462 600 Rev D ...
Page 24: ...Section 4 Technical Data 24 3BSE069462 600 Rev D ...
Page 32: ...PP882 Outline Section 6 Operator Panel Drawings 32 3BSE069462 600 Rev D ...