80
PCS100 UPS-I
User Manual
Table 10
-
1: GDM Menu Index Table
10.3
Parameter Listing
Note:
The parameter adjustment ranges defined in the following section are not necessarily achievable due to system
constraints.
Note:
Some parameter visibility depends on the login level of the user.
NOTICE
–
Trained Operators
All operations on the PCS100 UPS-I must only be carried out by a trained Operator familiar with the
contents of this manual. Hazardous conditions could arise from incorrect adjustment.
10.3.1
Menu 000 General
000 General
The menu contains general system parameters
Name:
011 Login
Function:
To enable or disable access to the Operator menu or the Tech menu
Access:
Continuous
Note:
Enter “159” to access the Operator menu
Parameter
041 Date and Time
Function:
To enter the date and time
Format:
YYYY-MM-DD HH:MM:SS
Access:
Operator
Parameter:
051 System Reboot
Function:
Restarts all functions within two minutes
Access:
Tech
Range:
True / False
Setting Up:
Select “True” to reboot the PCS100 UPS
-I. The parameter will automatically set back to
“False” once the PCS100 UPS
-I has rebooted. Event 209 will be displayed in the event log.
Parameter:
052 Reset Power Quality
Function:
Clears the power quality events recorded in the Summary Page. See Section 7.1.7.
Access:
Operator
B13 Static IP mask
GDM C00 Network Status
C11 Actual DHCP active
C14 Actual IP gateway
C12 Actual IP address
C15 MAC address
C13 Actual IP mask
C16 Ethernet Status
GDM D00 Product Revision
D11 GDMIB boot product D21 GDM revision
D12 GDMIB boot revision D31 Vcanserver name
D13 GDMIB product
D32 Vcanserver revision
D14 GDMIB revision
D40 Fan Control Service