PCS100 UPS-I
User Manual
43
5
Red
Over temperature Error Comparator output
impossible, circuit fault
Replace Ultracapacitor
Monitor Board
6
Red
Overvoltage Error
Comparator output
impossible, circuit fault
Replace Ultracapacitor
Monitor Board
Solid
Green OK
Table 6
-
4: Ultracapacitor Monitor Board Mimic Panel description
Each warning state is ‘latched’ so if a problem is intermittent, the warning will stay present until acknowledged by
a reset. If the fault or warning status still exists at the time of reset, then the warning will continue to display its
warning status. If the condition has stopped, then the warning will fall to a lower priority warning until it is back
to OK.
6.1.2.3
Status LEDs
The Status LEDs give information on the status of different
parts of the Ultracapacitor Energy Storage Enclosure and
Ultracapacitor Monitor Board.
A description of each LED are described in Table 6-5.
UB MAIN
UB CRG
UB BYPASS
UB READY
ENC TMP
EPO ENG
STATUS
LB MAIN
LB CRG
LB BYPASS
LB READY
Figure 6
-
4: Ultracapacitor Monitor Board Status
LEDs
Status LED
Status
Description
Recommended Action
UB MAIN
On
UB string DC circuit breaker is in
tripped state
Resolve tripping condition
UB CRG
On
UB string DC charge switch is in
tripped state
Resolve tripping condition
UB BYPASS
On
UB string fault bypass switch
activated
Is the string meant to be
decommissioned?
If not return to 'Normal'
UB READY
On
UB string DC voltage is /-30 V
from PCS100 UPS-I DC bus voltage
Safe to close string DC circuit
breaker
Off
UB string DC voltage not /-30
V from PCS100 UPS-I DC bus voltage
Wait for string to charge
LB MAIN
On
LB string DC circuit breaker is in
tripped state
Resolve tripping condition
LB CRG
On
LB string DC charge switch is in
tripped state
Resolve tripping condition
LB BYPASS
On
LB string fault bypass switch
activated
Is the string meant to be
decommissioned?
If not return to 'Normal'