PCS100 AVC-20
User Manual
91
10.4.2.5
Description of Power Quality Event Notification
Below is an example of a typical email sent to notify the customer of a power quality event.
From:
Sent:
Tuesday, 22 September 2015 10:52 a.m.
To:
Customer <
Subject:
Power Quality Event 12345678
Customer:
ABB NZ
Site Name:
Napier
Plant Name:
Site 1
Site Information
Note:
AVC connected to Production Line 75
Note:
Feeder 12 O/G
Product type:
PCS100 AVC-20
Model:
Product Rated voltage:
480.00V
Product Information
Product Rated Power:
1000kVA
Date
2015-09-21
Date and Time
Time 10:49:38.27
Input voltage V1
80%
Input voltage V2
82%
Utility sag at input to PCS100 AVC-20
Input voltage V3
87%
Output voltage V1
100%
Output voltage V2
100%
PCS100 AVC-20 sag correction
Output voltage V3
99%
Duration
200 ms
Sag duration
Event type
sag
Type of PQ event
System Status
running
Status of PCS100 AVC-20