74
PCS100 AVC-20
User Manual
Code
Origin
Type
GDM Info
Description
Recommended Action
61
R, I
F
Transistor
Case
OverTemp
The inverter’s (or rectifier’s)
IGBT (Insulated Gate Bipolar
Transistor) case
temperature is too hot
(over the limit).
Note: The temperature is
calculated using a thermal
model
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
62
R, I
W/AB
Transistor
Junction Hot
The IGBT junction is too hot
(near limit).
Note: The temperature is
calculated using a thermal
model.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
63
M, R, I
W/AB
Copper Hot
The choke winding is too
hot (near limit).
Note: The temperature is
calculated using a thermal
model.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
64
R,I
AB
Copper Over
Temp
The choke winding is too
hot.
Note: The temperature is
calculated using a thermal
model.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
65
I
AB
Bypass Over
Temp
Long duration bypass over
temperature detected.
None
66
M
W
Transformer
Hot
Transformer is too hot.
Note: The temperature is
detected by a thermistor in
transformer winding.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
67
M, R, I
W
VCAN
Warning
There is sustainable
interference in the module
communications cables.
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
68
M, R, I
F
VCAN Error
There was a non-
recoverable
communications error
between the master and the
inverter.
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
69
M
F
Rectifier Lost The Master controller lost
communications with
Rectifier module.
- Check ribbon cables between
modules
- Call service agent
70
M
F
Inverter Lost The Master controller lost
communication with the
Inverter module.
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.