background image

 

WARNING!: 

Be sure power is off before terminating the OVRHTE leads.

Raceway:

 To route OVRHTE conductors to the panel being 

protected, choose from any of these materials: (1) non-metallic 
flexible conduit, (2) metallic flexible conduit, (3) rigid conduit or 
(4) a nipple. The OVRHTE enclosure is provided standard with a 
19.1 mm (.75 in.) hub which will accept rigid or IMC conduit. A 
plastic flexible conduit with fitting and a 76.2 mm (3 in.) nipple 
are available as options.

Wire length:

 Use the supplied 609.0 mm (24 in.), 5.26 mm

(#10 AWG) leads. Trim leads to suit the application but do NOT 
splice to add length to the leads. Refer to Figures 1–4 for the 
color code of the OVRHTE leads. Terminate the leads as shown. 
(Note: For optimum performance, keep leads as short as 
possible and avoid sharp bends.)

Overcurrent protection: 

OVRHTE leads must be protected with 

an overcurrent protection device (circuit breaker or fuse) rated 
at 20 amps. Use a 3-pole breaker for 3-phase units or a 2-pole 
breaker for single-phase units.

Dry Contacts:

 For OVRHTE units with optional dry contacts, 

use butt splices within the panelboard to connect the dry 
contacts leads to the user’s monitoring circuits. Alternatively, 
install a junction box between the OVRHTE and the panelboard 
to connect dry contacts leads to user’s monitoring circuits. 

(

See Figure 6). Consult applicable local codes to ensure proper 

installation.

Before applying power

–  Measure the line to line voltage at the panel to be protected 

and be sure it is within ±10% of rated line to line voltage of 
the OVRHTE. Use the following table to determine the range 
of acceptable voltage for each model of OVRHTE.

Acceptable voltage ranges for All OVRHTE models

OVRHTE 

Nominal 

L-L voltage range 

model number 

voltage 

OVRHTExx1201P 120V 

N/A

OVRHTExx2401P 240V 

N/A

OVRHTExx1202S 

120/240V 

216 to 264

OVRHTExx1203Y 

120/208V 

188 to 228

OVRHTExx2203Y 

220/380V 

342 to 418

OVRHTExx2403Y 

240/415V 

374 to 457

OVRHTExx2773Y 

277/480V 

432 to 528

OVRHTExx3473Y 

347/600V 

540 to 660

OVRHTExx2403H 

120/240V 

216 to 264

OVRHTExx2403D 

240V 

216 to 264

OVRHTExx3803D 

380V 

342 to 418

OVRHTExx4803D 

480V 

432 to 528

Where “xx” = 25, 50, 80, 100 kA per mode

 

WARNING!: 

Do not apply power if the measured voltage is not within 
the range specified for the OVRHTE model being installed.

Electrical connections

6  Product manual | 

OVRHTE surge protective devices

Summary of Contents for OVRHTE

Page 1: ...Type 2 SPD applications Protects facilities and equipment against the harmful effects of lightning strikes and internally generated electrical transients Includes pre wired pigtail conductors to streamline installation Features internal copper bus conduction path to minimize system impedances lowering clamping voltage and increasing protection ...

Page 2: ...isconnecting the OVRHTE series units conductors including phases neutral and ground Warning lnstallation by person with electrotechnical expertise only Warnung lnstallation nur durch elektrotechnische Fachkraft Avertissement lnstallation uniquement par des personned qualifiées électrotechnique iAdvertencia La instalación deberá ser realizada únicamente por electricistas especializados Thank you fo...

Page 3: ... A model number is on the right side of the OVRHTE series unit Each model number corresponds to the configurations printed in Table 1 Model number Voltage Configuration OVRHTExx1201P 120V 1 phase 2 wire ground OVRHTExx2401P 240V 1 phase 2 wire ground OVRHTExx1202S 120 240V 2 phase 3 wire ground OVRHTExx1203Y 120 208V 3 phase Wye 4 wire ground OVRHTExx2203Y 220 380V 3 phase Wye 4 wire ground OVRHTE...

Page 4: ...o BOND CONDUCTORS FURNISHED WITH OVRHTE SERIES L1 L1 N N G N G L Figure 2 2 phase 3 wire 20 AMP 2 POLE CIRCUIT BREAKER OVRHTExx2S SERIES L1 L2 G N EARTH GROUND Xo BOND CONDUCTORS FURNISHED WITH OVRHTE SERIES L1 N L2 N G L1 L2 N G Figure 3 3 phase Wye 4 wire 20 AMP 3 POLE CIRCUIT BREAKER OVRHTExx3Y SERIES EARTH GROUND Xo BOND B N C A N G N G CONDUCTORS FURNISHED WITH OVRHTE SERIES A B C G N A B C 2...

Page 5: ...ive devices Product manual 5 Figure 6 Mounting hole detail Four 7 9 mm 3125 in holes are provided for mounting the OVRHTE Mounting 25 4 mm 1 in 101 6 mm 4 in 190 5 mm 7 5 in HUB 152 4 mm 6 in 171 5 mm 6 75 in 9 5 mm 375 in ...

Page 6: ...ces within the panelboard to connect the dry contacts leads to the user s monitoring circuits Alternatively install a junction box between the OVRHTE and the panelboard to connect dry contacts leads to user s monitoring circuits See Figure 6 Consult applicable local codes to ensure proper installation Before applying power Measure the line to line voltage at the panel to be protected and be sure i...

Page 7: ...2 5VA AC 457 0 mm 18 in of 19 1 mm 75 in nonmetallic flexible conduit and a fitting that connects to the provided 19 1 mm 75 in hub 19 1 mm 75 in x 76 2 mm 3 in nipple that connects to the provided 19 1 mm 75 in hub Standards Compliance Listed by UL to UL 1449 4th Edition for Type 2 SPD application cUL and UL1283 Compliant to IEEE C62 41 1 2002 C62 41 2 2002 and C62 45 2002 NFPA 70 NEC Article 285...

Page 8: ...hall apply ABB assumes no responsibility for any errors or omissions that may appear in this document We reserve all rights in this document and in the information contained therein Without prior written approval from ABB reproduction disclosure to third parties or use of any information in whole or in part is strictly forbidden Copyright 2016 ABB all rights reserved 072816 Model Date of purchase ...

Reviews: