CAUTION:
Do not assume the circuit is de-energized! Remove power
before performing any maintenance to these devices.
OVRHS3 mounting
Connecting the remote contacts to an alarm
(If option chosen on the OVRHS3U)
For “Fail-safe” Form A monitoring, connect the alarm leads
to terminals 2 and 3. Terminals 2 and 3 will be closed during
normal (Power ON) operation and the protector is functioning
properly. If the protector should fail contacts 2 and 3 will open
and contacts 1 and 2 will close. Relay contacts are rated at 5A
at 250Vac or 30Vdc maximum, 50mVA minimum.
Relay contacts shown in the relaxed position
(protector alarm or loss of power).
Note:
Maximum torque on terminals
is 10 in-lbs.
RE
M
OT
E
AL
AR
M
1
2
3
1
2
3
Protector
Service Panel Side
N
G
Electrical Service Entry
Protector
Service
Panel Side
Mounting
Surface
Ground
N
G
L
Neutral
Bars
Circuit Breaker
N
G
Locknut
Surge Suppressor
Line Wire
OVRHS3-F1 mounting
OVRHS3U mounting
OVRHS3/OVRHS3U surge protective devices
| Product manual 7