17
Diagnostics
In case of a fault or alarm signal, check for and correct:
Note:
The validity of the encoder signal is also checked during the
ID-run. See parameter 9910
MOTOR
ID
RUN
. If the drive detects an
encoder problem during the ID-run, the drive provides an alarm.
Parameter 5003
FAULT
ENABLE
controls the drive’s fault/alarm response
to encoder errors only after the ID-run is completed.
Code
Name In
Panel
Description and Recommended Corrective Action
23
ENCODER
ERR
The drive is not detecting a valid encoder signal. Check for
and correct:
• Encoder presence and proper connection (reverse wired,
loose connection, or short circuit).
• Voltage logic levels are outside of the specified range.
• Pulse Encoder Interface Module, OTAC-01, presence and
proper connection to the ACS550.
• Wrong value entered in parameter 5001
PULSE
NR
. A
wrong value will only be detected if the error is such that
the calculated slip is greater than 4 times the rated slip of
the motor.
• Encoder is not being used, but parameter 5002
ENCODER
ENABLE
= 1 (