Functions
Unscrew the cap on top of the active unit to access the dip-switches.
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
NB: Each function is associated with two different dip-switches: the top and bottom dip-switches must be configured in
the same manner. The “ON” position is the position at delivery.
The dip-switches allows to set the functions as described in the following table:
Dip-switches
Function
ON*
OFF
1
Muting timeout
10 min
∞
2
T / X or L-muting
T / X-muting
L-muting
3
Muting filter
Deactivated
Activated
4
Reset of the Override
Manual
Automatic
5
Not used
-
-
6
EDM
Deactivated
Activated
7
Reset
Automatic
Manual
8
Not used
-
-
*Factory default configuration
Warning!
An infinite muting (timeout =
∞
) is not compliant with EN 61496-1:2013. Therefore, all possible risks must be
considered and related precautions undertaken before selecting the option “
∞
”.
Warning!
The device does not accept configuration changes during normal operation. A change is taken into account
after the next powering of the device. Therefore, the management and the use of the configuration dip-switches
should be performed with great care.