Appendix A – Parameter Listings
Installation and Start-up Guide for NPBA-01
A-3
24
ACTUAL VALUE 1
ACT VAL1
PID controller Actual value 1
Available only if the PID
Macro is selected
10000 100 %
25
ACTUAL VALUE 2
ACT VAL2
PID controller Actual value 2
Available only if the PID
Macro is selected
10000 100 %
26
CONTROL
DEVIATION
CONT DEV
The difference between the
reference given by the user
and the actual reference the
ACS 600 is following
-10000
-100
%
PROFIBUS
Par. No.
(Add 4000 in
FMS Mode)
ACS 600 Parameter
Alternative Settings
Scaling
10 START/STOP/DIR
101
10.1 EXT1 STRT/STP/DIR
1 = NOT SEL; 2 = DI1; 3 = DI1,2; 4 = DI1P,2P; 5 = DI1P,2P,3; 6 = DI1P,2P,3P;
7 = DI6; 8 = DI6,5; 9 = KEYPAD; 10 = COMM.MODULE
102
10.2 EXT2 STRT/STP/DIR
103
10.3 DIRECTION
1 = FORWARD; 2 = REVERSE; 3 = REQUEST
11 REFERENCE SELECT
126
11.1 KEYPAD REF SEL
1 = REF1(rpm); 2 = REF2(%)
127
11.2 EXT1/EXT2 SELECT
1 = EXT1; 2 = EXT2; 3 ... 8 = DI1 ... DI6; 9 = COMM.MODULE
128
11.3 EXT REF1 SELECT
1 = KEYPAD; 2 ... 4 = AI1 ...AI3; 5 = AI1/JOYST; 6 = AI2/JOYST; 7 = AI1+AI3;
8 = AI2+AI3; 9 = AI1-AI3; 10 = AI2-AI3; 11 = AI1*AI3; 12 = AI2*AI3;
13 = MIN(AI1,AI3); 14 = MIN(AI2,AI3); 15 = MAX(AI1,AI3); 16 = MAX(AI2,AI3);
17 = DI3U,4D(R); 18 = DI3U,4D; 19 = DI5U,6D; 20 = COMM.MODULE
129
11.4 EXT REF1 MINIMUM
0 ... 18000 rpm
1 1 rpm
130
11.5 EXT REF1 MAXIMUM
131
11.6 EXT REF2 SELECT
1 = KEYPAD; 2 ... 4 = AI1 ...AI3; 5 = AI1/JOYST; 6 = AI2/JOYST; 7 = AI1+AI3;
8 = AI2+AI3; 9 = AI1-AI3; 10 = AI2-AI3; 11 = AI1*AI3; 12 = AI2*AI3;
13 = MIN(AI1,AI3); 14 = MIN(AI2,AI3); 15 = MAX(AI1,AI3); 16 = MAX(AI2,AI3);
17 = DI3U,4D(R); 18 = DI3U,4D; 19 = DI5U,6D; 20 = COMM.MODULE
132
11.7 EXT REF2 MINIMUM
0 % ... 100 %
10000 100 %
133
11.8 EXT REF2 MAXIMUM
0 % ... 500 %
5000
500
%
PROFIBUS
Par. No.
(Add 4000 in
FMS Mode)
Name
Short name
Description
Scaling
0 %
0
0 %
0
10000
100 %
0
0 %
0
0 %