Installation and maintenance instruction

Fläkt Woods three phase asyncronous motor 

Manufacturer: ABB

Spare parts

When ordering spare parts, the full type designation and

product code, as stated on the rating plate, must be

specified.

If the machine is stamped with a serial manufacturing

number, this should also be given.

Environmental requirements

Noise levels

Smaller machines have a sound pressure level that not 

exceeding 70 dB(A).
The following table shows catalogue values of sound 

pressure levels at 1 m from the machine surface.

Values for specific machines can be found in the relevant 

product catalogues. Tolerance acc ± 3 dB(A).
The table values refer to 50 Hz sinusoidal supply

conditions.

For 60 Hz sinusoidal supply, add 4 dB(A) to the above

values.
For sound pressure levels with non-sinusoidal supplies,

contact ABB Sales Office.
Sound pressure levels for all machines in the above 

frame sizes having separate cooling systems and for

series M2F*/M3F*, M2L*/M3L*, and M2R*/M3R*, are

indicated in separate specific Machine Instructions.

Rewinding

Rewinding should always be carried out by qualified 

repair shops.
Smoke venting and other special motors should not be

rewound without first contacting ABB Motors.

Guideline sound pressure level, dB(A)

Frame size

2 pole

4 pole

6 pole

8 pole

132

69

59

61

56

160

69

62

59

59

180

69

62

59

59

200

72

63

63

60

225

74

66

63

63

250

75

67

63

63

280

77

68

66

65

315

80

71

68

72

355

83

80

75

75

400

83

80

-

-

Summary of Contents for MT series

Page 1: ...act bearing Motors equipped with regreasing devices When starting the motor for the first time apply at least the specified quantity of grease until new grease forced outofthegreaseoutlet Fordetailsse...

Page 2: ...and or angular contact bearings must be fitted with locking devices during transport Lifting Onlyliftthemotorusingtheliftinglugs The center of gravity of motors with the same frame may WARNING Small m...

Page 3: ...catalogues Unused cable entries must be closed As well as main winding and earthing terminals the terminalboxcanalsocontainconnectionsforthermistors standstill heating elements bimetallic switches or...

Page 4: ...hepartsandreplaceifnecessary Lubrication Machines with permanently greased bearings Machines up to frame size 180 are normally fitted with permanently greased bearings of either Z or 2Z types Bearingt...

Page 5: ...or is higher than 400 000 calculated as Dm x n where Dm average bearing diameter mm n rotational speed rpm The following or similar types of grease can be used Kluber Asonic GHY 72 Kluber Asonic HQ 72...

Page 6: ...erelevant product catalogues Tolerance acc 3 dB A The table values refer to 50 Hz sinusoidal supply conditions For 60 Hz sinusoidal supply add 4 dB A to the above values For sound pressure levels with...

Page 7: ...open Check lines for open phase Wrong application Change type or size Consult manufacturer Overload Reduce load Low voltage Ensure the name plate voltage is maintained Check connection Open circuit Fu...

Page 8: ...e Fan rubbing air shield Remove interference Fan striking insulation Clear fan Loose on bedplate Tighten holding bolts Noisy operation Airgap not uniform Check and correct bracket fits or bearing Roto...