ABB SACE
3
Technical data
Reference Standards
ABB SACE L.V. MNS R switchgear
Standards conformed to
CEI EN 60439-1, IEC 439-1
Test certification
Test certificates
ABB SACE, ACAE LOVAG and SINAL
Electrical Data
Rated voltages
Rated insulation voltage
up to 1000 V AC 1500 V DC
Rated service voltage Ue
up to 690 V AC 750 V DC
Rated frequency
50 - 60 Hz
Impulse withstand voltage
12 kV
Rated currents
Main busbars:
Rated current
up to 6300 A
Rated peak withstand current
up to 220 kA
Rated short-time withstand current (1s)
up to100 kA
Distribution busbars:
Rated current
630
÷
4000 A
Rated peak withstand current
220 kA
Rated short-time withstand current (1s)
100 kA
Arc-proof
Values
100 kA, 0,3 s. at
IEC 61641 (on request)
Mechanical
Dimensions
Height
2200 mm
characteristics
Widht
300, 400, 600, 800, 1000, 1200 mm
Depth
1025, 1200, 1400, 1600 mm
Module base (height)
E = 25 mm DIN 43660
Surface protection
Frame
Al-Zn galvanisation
Internal divisions
Galvanised sheet UNI EN 10130
Transversal section
Electrolytic galvanisation UNI ISO 4520
Housing (doors and external curtain panels)
Painting RAL 7035
Degrees of protection
With door open
IP20
IEC 529, EN 60529 Standards
With door closed
IP30 standard, up to IP 54
Construction form
3a, 3b, 4b
Normal conditions
Installation
internal for service
Ambient temperature
-5
°
C; +40
°
C
Relative humidity
max. 50% at 40
°
C
Max. altitude
)
2000 m
Extra options
Paint
External protection
colour on request
Busbar system
Main and branch busbars
sheathed busbars, treated busbars (Ag/Sn)
Forms of segregation
According BS 60439-1
4b type 1
÷
7
ABB PC30
23-11-2009, 8:12
3
415 V
Summary of Contents for MNS R