16
ABB SACE
P
A
B
C
1025
450
525
50
1200
450
400
350
525
225
1400
450
525
425
650
300
1600
450
525
625
650
500
FRONT
Switchgear depth
The switchgear can have different
depths. Selection mainly depends on
the rated current of the main busbar
system, on the short-time withstand
current and on the space needed for
feeder connections.
Depth
Standardisation
Switchgear depth in relation to the main busbars rated current
Amperes
Depth
Max. 50 kA
400
1200
630
1200
800
1200
1000
1200
1250
1200
1600
1200
2000
1200
2500
1200
Max. 75 kA
400
1025-1200
630
1025-1200
800
1025-1200
1000
1025-1200
1250
1025-1200
1600
1025-1200-1400
2000
1025-1200-1400
2500
1025-1200-1400
3200
1025-1200-1400-1600
Max. 100 kA
3200
1400-1600
4000
1400-1600
5000
1400-1600
6300
1400-1600
ABB PC30
23-11-2009, 8:14