SETTINGS – IP CONFIGURATION
CONFIGURATIONS
36
1TGC908004
Broadcast Address LAN3
192.168.171.255
Calculated automatically
Default Gateway LAN3
192.168.171.1
LAN 3 is not used
Time Synchronization
RTC
RTC,
NTP
RTC=internal clock, NTP=if external
NTP server is available
Time Server Address
0.0.0.0
Settings according to network
administrator
Table 11 Digital Gateway Default Parameters – IP Configuration
7.2.
Settings – IP Configuration
All configuration settings and parameterization for the Digital Gateway are configured with
the MNavigate software tool.
Figure 30 IP Address Settings
Figure 31 Time Sync Settings
Digital Gateway does not support DHCP service to get automatic network ad-
dress. If the default IP Address and Subnet Mask must be manually adjusted, the
parameter above has to be modified and copied to the Digital Gateway. Any
change in the address requires the Digital Gateway to be restarted before the
change is activated.
It has to be ensured that the Subnet address (
xxx.xxx.xxx
.yyy) for LAN1, LAN2 &
LAN3 port is different. For example, LAN1 =
192.168.100
.100 and LAN2 =
192.168.200
.100