DATA MAPPING
DEFAULT DATA MAP
1TGC908004
53
Modbus
Function
Code
Modbus
Register
Device
Number
Description
Remarks
2
13671
128
CCW or K2
1 = Motor Runs Coun-
ter Clockwise
2
13672
128
Ready
1 = Off and Ready for
Operation. No
alarm/trip is available
2
13673
128
Alarm
1 = Any Alarm condi-
tion of protection or
supervision functions.
2
13674
128
New Trip
1 = Any Trip condition
of the protection or
supervision functions
2
13675
128
Test
1 = Main switch set to
test position. (Motor
cannot start)
2
13676
128
HW local
1 = Control Access is
selected to hardwired
I/O from Local / Re-
mote input on M10x
2
13677
128
Bus local
1 = Control Access is
passed to any control
station on the switch-
gear control network.
2
13678
128
Remote
1=Control Access is
passed to the Process
Control System
2
13679
128
DI0
1= Digital Input 0 of
M10x is on
2
13680
128
DI1
1= Digital Input 1 of
M10x is on
2
13681
128
DI2
1= Digital Input 2 of
M10x is on
2
13682
128
DI3
1= Digital Input 3 of
M10x is on
2
13683
128
DI4
1= Digital Input 4 of
M10x is on