3  Easy Setup

1  Log on to the LMT at the Standard or Advanced access level.

2  Select Easy Setup in the main menu.

3  Select a language in the “Easy Setup” menu and press 

 .

4  Select available option of primary variable in the “Easy 

Setup” menu and press 

 .

5  Select available option of units of measure in the “Easy 

Setup” menu and press 

 .

6  Set LRV in the “Easy Setup” menu and press 

 .

LRV is the lower range value which corresponds to 4 mA current 
out value.

7  Set URV in the “Easy Setup” menu and press 

 .

URV is the upper range value which corresponds to the 20 mA 
current out value.

8  Set Damping time in the “Easy Setup” menu and press 

 .

Damping allows smoothing step response in the device output.

9  Select displayed variable in the “Easy Setup” menu and  

press 

 .

Sets the selected process variable on the first line on the 
process display.

10 Set a tag in the “Easy Setup” menu and press 

 .

A tag is a quick way to identify the device.

*For detailed commission/operation steps refer to LMT 
operating instructions.

Summary of Contents for LMT100

Page 1: ...ABB MEASUREMENT ANALY TICS COMMISSIONING INSTRUCTIONS LMT Series Magnetostrictive level transmitter LMT100 200 models Quick Start Guide K TEK Level products Measurement made easy...

Page 2: ...2 LMT SERIES MAGNETOSTRICTIVE LEVEL TR ANSMITTER LMT100 200 MODELS CI LMT100 200 EN REV B Sales Service Contents 1 Electrical Connections 4 2 Mounting 4 3 Easy Setup 5...

Page 3: ...r systems according to safety engineering standards for electrical circuits high pressures and aggressive media Training or instruction in accordance with safety engineering standards regarding mainte...

Page 4: ...lator 5 PLC DCS 6 HART Handheld terminal 7 External indicator 8 External earthing terminal 9 Terminal for external indicator 0 Laptop LMT100 Transmitters installations A Installed in external chambers...

Page 5: ...y Setup menu and press LRV is the lower range value which corresponds to 4 mA current out value 7 Set URV in the Easy Setup menu and press URV is the upper range value which corresponds to the 20 mA c...

Page 6: ...RT mode 4 0mA at 36 0 Vdc 0 144 watts at 12 0 Vdc 0 048 watts Ambient temperature 40 to 85 C 40 to 185 F Ambient Humidity 0 to 100 RH Electrical connection Two M20 x 1 5 or two 1 2in FNPT adapters and...

Page 7: ...LMT SERIES MAGNETOSTRICTIVE LEVEL TR ANSMITTER LMT100 200 MODELS CI LMT100 200 EN REV B 7...

Page 8: ...illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Copyright 2018 ABB A...

Reviews: