M AG N E TOS T R I C T I V E L E V EL T R A N SM I T T ER L M T 10 0 & 2 0 0 M O D EL S | C I/L M T 10 0/ 2 0 0 - EN R E V. B
5
3 Easy Setup
1 Log on to the LMT at the Standard or Advanced access level.
2 Select Easy Setup in the main menu.
3 Select a language in the “Easy Setup” menu and press
.
4 Select available option of primary variable in the “Easy
Setup” menu and press
.
5 Select available option of units of measure in the “Easy
Setup” menu and press
.
6 Set LRV in the “Easy Setup” menu and press
.
LRV is the lower range value which corresponds to 4 mA current
out value.
7 Set URV in the “Easy Setup” menu and press
.
URV is the upper range value which corresponds to the 20 mA
current out value.
8 Set Damping time in the “Easy Setup” menu and press
.
Damping allows smoothing step response in the device output.
9 Select displayed variable in the “Easy Setup” menu and
press
.
Sets the selected process variable on the first line on the
process display.
10 Set a tag in the “Easy Setup” menu and press
.
A tag is a quick way to identify the device.
*For detailed commission/operation steps refer to LMT
operating instructions.