LME / RSD10 / RSD20 / RSD50 / RSD100 (Contrac)
ELECTRICAL LINEAR ACTUATOR | OI/LME/RSD10/100-EN REV. E
19
Conductor cross-section on electronic unit
Note
Detailed information on separate electronic units can be found
in the corresponding data sheets.
EAN823 – screw terminals
Motor/brake
rigid: 0.2 to 6 mm
2
(24 to 10 AWG)
flexible: 0.2 to 4 mm
2
(24 to 12 AWG)
Mains
rigid: 0.5 to 6 mm
2
(20 to 10 AWG)
flexible: 0.5 to 4 mm
2
(20 to 12 AWG)
Signals
rigid: 0.5 to 6 mm
2
(20 to 10 AWG)
flexible: 0.5 to 4 mm
2
(20 to 12 AWG)
EBN853 – Screw terminals
Motor/brake
rigid: 0.2 to 6 mm
2
(24 to 10 AWG)
flexible: 0.2 to 4 mm
2
(24 to 12 AWG)
Mains
rigid: 0.5 to 6 mm
2
(20 to 10 AWG)
flexible: 0.5 to 4 mm
2
(20 to 12 AWG)
Signals
rigid: 0.5 to 4 mm
2
(20 to 12 AWG)
flexible: 0.5 to 2.5 mm
2
(20 to 14 AWG)
EBN861 – Screw terminals
Motor / brake
rigid: 0.2 to 6 mm
2
(24 to 10 AWG)
flexible: 0.2 to 4 mm
2
(24 to 12 AWG)
Mains
rigid: 0.5 to 6 mm
2
(20 to 10 AWG)
flexible: 0.5 to 4 mm
2
(20 to 12 AWG)
Signals
rigid: 0.5 to 4 mm
2
(20 to 12 AWG)
flexible: 0.5 to 2.5 mm
2
(20 to 14 AWG)
EAS822 – Clamping connection
Suited for cable Ø Terminals for conductor
cross-section
Mains cable
13 mm (0.51 in)
max. 4 mm
2
(12 AWG)
Signal cable (DCS)
8 mm (0.31 in)
max. 1.5 mm
2
(16 AWG)
Transmitter (option)
8 mm (0.31 in)
max. 1.5 mm
2
(16 AWG)
Motor cable
13 mm (0.51 in)
max. 4 mm
2
(12 AWG)
Sensor cable
8 mm (0.31 in)
max. 1.5 mm
2
(16 AWG)
EBS852 – Clamping connection
Suited for cable Ø Terminals for conductor
cross-section
Mains cable
13 mm (0.51 in)
max. 4 mm
2
(12 AWG)
Signal cable (DCS)
8 mm (0.31 in)
max. 1.5 mm
2
(16 AWG)
Transmitter (option)
8 mm (0.31 in)
max. 1.5 mm
2
(16 AWG)
Motor cable
13 mm (0.51 in)
max. 4 mm
2
(12 AWG)
Sensor cable
8 mm (0.31 in)
max. 1.5 mm
2
(16 AWG)
EBS862 – Clamping connection
Terminals for conductor cross-section
Mains cable
max. 6 mm
2
(10 AWG)
Signal cable (DCS)
max. 4 mm
2
(12 AWG)
Transmitter (option)
max. 4 mm
2
(12 AWG)
Motor cable
max. 6 mm
2
(10 AWG)
Sensor cable
max. 4 mm
2
(12 AWG)
Cable glands
The actuators and electronic units are supplied without cable
glands. Suited cable glands must be installed on site.
Tap holes for cable glands
metric
optional adapters for*
Signals
M20 × 1.5 (2 ×)
PG 16 (2 ×)
NPT ½ in (2 ×)
Motor
M25 × 1.5 (1 ×)
PG 21 (1 ×)
NPT ¾ in (1 ×)
* Adapter for PG or NPT thread must be ordered separately
Selection of suited connection cables
Please observe the following information when selecting cables:
• Use shielded cables for the motor/brake cable, the
sensor cable, and the signal cable to the control
system/controller.
• Connect the shielding of the motor/brake cable and the
sensor cable on both sides (to the actuator and to the
Contrac electronic unit).
Change from two to one column