SPS
-
48V Shelf_QSG
Rev. 2.0
Specifications and Application
•
Specifications and ordering information are in the Slimline Power System Brochure available at
•
External Surge Protective Devices (SPDs)
-
are required on all AC inputs.
Equipment Safety is Approved in IEC 60664
-
1 Installation Category II environments.
•
Equipment and subassembly ports:
1. are suitable for connection to intra
-
building or unexposed wiring or cabling;
2. can be connected to shielded intra
-
building cabling grounded at both ends.
•
Grounding / Bonding Network –
Connect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated
Ground Plane (Mesh
-
Bonding Network or Common Bonding Network).
•
Installation Environment
-
Install in Network Telecommunication Facilities, OSP, or where NEC applies.
•
Battery return may be either Isolated DC return (DC
-
I) or Common DC return (DC
-
C).
Reference Documents
These documents are available at
Document Title:
850035894 Galaxy Pulsar Edge Quick Start Guide
CC848836981 Pulsar Edge Controller Family Product Manual
Temperature:
North America –
50°C Max. with no derating. 2% / °C derating above 50°C to 75°C.
CE –
50°C Max.