FUNCTIONALITY

 

In normal condition, with insulation value higher than the set threshold, the instrument has the green LED on.  

Pressing the TEST button, the TRIP LED of alarm signalling and the output relay will be activated.  

Depending on the connection, the RESET will be automatic when the TEST button is released, or using a re-
mote button, or manually using the RESET button on the front panel.  

If there is low insulation on the line (resistance value under the set threshold), the TRIP signalling and the out-
put relay will be activated.  

When the insulation on the line comes back higher than the set threshold, the trip signalling will disappear. 

 

 

TECHNICAL FEATURES

 

Auxiliary voltage supply 

230V 50-60Hz ± 20% or 110V 50-60Hz ± 20% 

Maximum consumption 

3 VA 

Network to control 

24 ÷ 10% (760V on three-phase line with neutral) 

Measure voltage 

Max 24V 

Measure current 

Max 0,5 mA 

Internal impedance 

100 

 

Threshold tripping 

Settable 10 ÷ 150 

 (4 level with micro-switches) 

Tripping delay 

About 1 second 

Signalling and button 

Led ON, led TRIP; TEST and RESET button 

Output 

Relay changeover contact NA-C-NC max 5A 250Vca 

Working and storing temperature 

 -10 ÷ 60°C / -20 ÷ 70°C 

Relative humidity 

≤ 95 %

 

Insulation test 

3 kV 60 sec. / 4 kV imp. 

1,2/50μs

 

Mounting position 

Any 

Wiring type 

Screw terminals / cross section cables 4 mm² 

Protection degree 

Front with cover: IP 40 

 Enclosure: IP 20 

Mounting according DIN 50022 

Snap on DIN rail 35mm / 3 modules 17,5 mm 

Weight 

About 300 g 

Standards 

Safety IEC-EN 61010-1 

Product IEC-EN 61557-8 

Electromagnetic compatibility IEC-EN 61326-1 

 

For application not described in this manual it’s better to see specific document or to contact the technical 

service. 

 

NOTE 

At reason of the evolution of standards and products, the company reserves to modify in every time the features of the product described 

in this document, that it’s

 necessary to verify preventively. 

The liability of the producer for damage caused by defect of the product ”can 

be reduced or deleted (…) when the damage is caused joint by a defect of product or

 for blame of the damaged or a person of which the 

damaged is responsible” (Article 8, 85/374/CEE).

 

 

 

1

 

 

Reviews: