LEGEND

 

Auxiliary power supply 

Terminals 1-3 

The auxiliary power supply can be the same as the network to control. 

Insulation control 

Terminals 5-11 

The two terminals must be connected between the line under control and the earth measurement reference. 
Terminal 5 must be connected to the neutral conductor of the single-phase or the three-phase line under con-
trol. If the three-phase network has three wires, the terminal must be connected to a phase. The maximum 

voltage required between these terminals is 440V, and for this reason, it’s possible to use the insulation con-

troller on a single-phase line or on a three-phase line with 3 wires without neutral up to 440V and with 4 wires 
with neutral up to 760V. 

Relay output connections 

Terminals 7-8-9 

For remote signalling by relays with changeover contact max 5A 250V on resistive load. 

Automatic or remote RESET connection 

Terminal 12 

By connecting terminal 12 to terminal 11 (ground), a manual RESET function is possible (using the pushbutton 
on the front of the instrument). Without the connection at terminal 12, the instrument will function with 
automatic RESET when the low insulation condition ceases. An external N.C. contact push-button can be 
connected between the monitoring device and the ground. 

 

 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

 

 
 

 

 

DIMENSIONS

 

Snap on DIN rail 35mm

 

(DIN 50022)

 

3 modules 17,5 mm

 