Smart Buildings
Product Overview
28 9AKK107992A0761 EN Rev. B | IS/S 8.1.1, ISP/S 8.1.1
Note about navigation in the PDF: Key combination 'Alt +
left arrow' jumps to the previous view/page
3.5.7
EMC and immunity
EMC interference emission
Radiated emission
FCC 47 CFR Part 15
Class A
EN 55032
Class A
EN 61000-3-2
Class A
EN 61000-6-4
Fulfilled
Conducted emission
FCC 47 CFR Part 15
Class A
EN 55032
Class A
EN 61000-3-2
Class A
EN 61000-6-4
Fulfilled
EMC interference immunity
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge
±4 kV
EN 61000-4-2
IEEE C37.90.3
Air discharge
±8 kV
Electromagnetic field
EN 61000-4-3
80 MHz ... 1000 MHz
1000 MHz ... 6000 MHz
max. 10 V/m
max. 3 V/m
Fast transients (burst)
EN 61000-4-4
DC supply connection
2 kV
EN 61000-4-4
Data line
2 kV (U/UTP)
4 kV (SF/UTP)
Voltage surges - DC supply connection
EN 61000-4-5
line/ground
2 kV Supply voltage
EN 61000-4-5
line/line
1 kV Supply voltage
Voltage surges - data line
EN 61000-4-5
line/ground
1 kV (U/UTP, SF/UTP)
Conducted disturbances
EN 61000-4-6
150 kHz ... 80 MHz
10 V
Immunity
IEC 60068-2-6, test Fc
Vibration
5 Hz ... 8.4 Hz with 3.5 mm amplitude
8.4 Hz ... 150 Hz with 1 g
IEC 60068-2-27, test Ea
Shock
15 g at 11 ms
Table 13: EMC and immunity