![ABB i-bus EIB Product Manual Download Page 5](http://html1.mh-extra.com/html/abb/i-bus-eib/i-bus-eib_product-manual_3371245005.webp)
ABB i-bus
®
EIB / KNX
Device technology
2 Device
technology
2.1 SA/M
2.6.1
Switch Actuator Module,
2-fold, 6 A
The 2-fold Switch Actuator Module is operated in any module slot of the
Room Controller Basis Device. Using relay contacts, it switches two
independent groups of electrical loads such as fluorescent lamps. The
outputs are distinguished by a high switching current.
Both the incoming supply and the internal voltage are supplied via the Room
Controller Basis Device. Contact is automatically established when the
modules are snapped in place.
2.1.1 Technical
data
Power supply / Incoming supply
– Operating voltage
made available by the Room Controller Basis
Device, contact made via contact system on
base of module
– Incoming supply
0...264 V AC, contact established via contact
surfaces at the front
Outputs
– 2 load circuits
Relay outputs
Max. switching current:
16 A / AC1, 10 A / AC3
Max. continuous current: 6 A
Max. inrush peak current I
p
:
400 A (150 µs), 320 A (250 µs)
– Contact endurance
10
7
mechanical
10
5
electrical (at 230 V / 16 A / AC1)
Connections
– Load circuits
2 x three-pole, plug-in screw terminals
– Wire ranges
0.2…2.5 mm
2
finely stranded
0.2…40 mm
2
single-core
Ambient temperature range
– Storage
-25 °C ... 55 °C
– Transport
-25 °C ... 70 °C
Design
– Type of installation
For snapping into the
Room Controller Basis Device
– Housing, colour
Plastic housing, anthracite, halogen-free
– Housing dimensions (WxHxD)
49 mm x 42 mm x 93 mm
– Weight
0.1 kg
CE norm
– in accordance with the EMC guideline and
the low voltage guideline
© 2004 ABB STOTZ-KONTAKT GmbH
5