ABB i-bus
®
EIB / KNX
Project design and programming
Note:
This parameter can be overwritten by the parameters which are
enabled in the “A: Function” parameter window.
4.3.2 Parameter
window:
“Function”
Basic settings for the function of an output are carried out in this parameter
window. Additional functions can also be enabled.
Parameter: “Reaction of output”
It can be set in this parameter whether the output operates as a “Normally
closed contact” or “Normally open contact”.
In the “Normally open contact” function, an ON command leads to the
closing of a contact while an OFF contact causes the contact to be opened.
When “Normally closed contact” is selected, the reverse process is carried
out.
Parameter: “Enable function ‘time, staircase lighting, flashing’”
This parameter enables the function “Time, staircase lighting, flashing”
(parameter window “A: Time”).
Parameter: “Enable function ‘presets’”
This parameter enables the “Preset” function (parameter window
“A: Presets”).
Parameter: “Enable function ‘scene: (8-bit)’”
The object “8-bit scene” is enabled via this parameter (parameter window
“A: Scene”).
Parameter: “Enable function ‘logic’”
This parameter enables the function “Logical connection, disable function”
(parameter window “A: Logic”).
Parameter: “Enable function ‘priority/forced operation, cyclic
monitoring’”
This parameter enables the safety functions “Cyclic monitoring, forced
operation” (parameter window “A: Safety”).
Parameter: “Enable threshold function”
This parameter enables the ‘Threshold value function” (parameter window
“A: Threshold”).