32
E LEC TRON I C COM PAC T STA RTE R
| M A N UA L
Signaling for ROLE-types
The following table shows the LED codes for ROL- and ROLE- device diagnostics. An equivalent table can be found in the
package insert.
• HF0.6-ROLE-24VDC
• HF2.4-ROLE-24VDC
• HF9-ROLE-24VDC
Operation Status
The electronic compact starter uses LEDs to indicate status messages for operation, fault and test:
Status
Description
PWR
ERR
L
R
Error acknow-
ledgment
LED colors on HMI (human machine interface)
Green
Red
Yellow
OFF
Supply voltage not present
OFF
OFF
OFF
OFF
-
Ready to operate
Supply voltage present
ON
OFF
OFF
OFF
-
Drive switched on
Reverse running (L)
ON
OFF
ON
OFF
Forward running (R)
ON
OFF
OFF
ON
Internal error
Internal device error –
device replacement required
ON
ON
OFF
OFF
Not possible
External error in the
controller or the I/O
devices (maintenance
requirement, NE44)
Bimetal function:
The motor current is higher than the nominal motor current
specification (e.g. Class 10A): Cooling time is running
(20 min.)
• An error occurred with left rotation (reverse running)
ON
Flashes
ON
OFF
Automatic
1)
• An error occurred with right rotation (forward running)
ON
Flashes
OFF
ON
Automatic
1)
After 2 minutes, the 'L' or 'R' flashes: a manual reset is
possible
• An error occurred with left rotation (reverse running)
ON
Flashes
Flashes
OFF
Manual
• An error occurred with right rotation (forward running)
ON
Flashes
OFF
Flashes
Manual
Error restoring the system state:
Checksum error. The
thermal memory of the motor protection function is set to
the maximum value. The error must be manually
acknowledged, also in automatic operation.
ON
Flashes
Flashes
Flashes
Manual
Symmetry:
The two motor currents deviate from each other
by more than 33%.
ON
Flashes
OFF
OFF
Manual
Blocking:
The max. measurable motor current is exceeded
for more than 2 sec..
• An error occurred with left rotation (reverse running)
OFF
Manual
Flashes
OFF
Manual
• An error occurred with right rotation (forward running)
ON
Flashes
OFF
Flashes
Manual
Message (power path
remains switched on)
Message with pending control signal:
- Two or more phases are missing
- No motor connected
- Motor current in at least two phases >2 sec. below the
minimum current value that can be set
• A message occurred during reverse running.
Flashes
Flashes
ON
OFF
Automatic
2)
• A message occurred during forward running.
Flashes
Flashes
OFF
ON
Automatic
2)
Table 13 Signaling ROLE-types
1) Bridge between the terminals 'RES' and 'AUT'
2) No other measures necessary
—
4.5
Function Test
General function test when U
S
is applied: After the control supply voltage U
S
is applied, all the LEDs light up once. The device
performs a diagnosis of the functions when the load is being switched on or when it is switched off.
Motor overload protection safety function test:
A skilled worker, well acquainted with the relevant standards, can conduct a 'motor overload protection' safety function test.
For this test, the load must be activated and the current flow in a conductor interrupted (e.g. by removing L1 or L3 phase).
The Electronic Compact Starter then switches off the load within 1.5-2 sec.. The LED for right rotation (forward running)
goes out and the ‘ERR’-LED and the reply output are set.