TR A N S FOR M E R BUS H I NG S T Y PE G SA - OO
T EC H N I C A L G U I D E
Solid rod is used for maximum current capacity and
stranded cable for greater ease of assembly, when the
required current capacity is lower. A mounting kit is used for
fixing and sealing the terminal to the bushing.
Mounting kit
The mounting kit, LF 170 087-A, is supplied with each
bushing and consists of a divided ring, a divided spring
washer, two O-rings and a top nut. One of the O-rings is
intended for use at site installation.
Included in each packing for delivery are two lifting eye bolts
M12, 2183 2001-3, and a hook spanner, 6896 743-1, intended
for use at installation.
Integrated inner/outer terminal
The integrated inner and outer terminal is available with
different inner diameters suited for different stranded
cables. Other configurations can be supplied on request.
Table 4.
Material and design
Conductor
diameter, D (mm)
Cat. No.
LF 170 084
Mass
(kg)
Copper for brazing
5
-A
4.1
11
-B
4.1
13
-C
4.1
15
-D
4.0
18
-E
4.0
30
-F
3.9
42
-G
3.6
45
-H
3.6
50
-I
3.4
54
-J
3.3
—
06 Mounting kit.
—
07 Inner/outer terminal.
—
Connection details
Top nut
65
35
D
13
26
M8
ø30
Terminal stud
Divided spring washer
Divided ring
O-ring