Electrical connection
26 - EN
FSM4000
D184B141U02
4.4
Connection examples for peripherals (incl. HART)
Current output
G00243
+31
-32
0/4 ... 20 mA
0/2 ... 10 mA
I
E
I = internal
E = external
Current output:
selectable in software
Function:
Active
0/4 ... 20 mA (0
Ω
≤
RB
≤
560
Ω
)
0/2 ... 10 mA (0
Ω
≤
RB
≤
1120
Ω
)
Terminals: 31, 32
(for HART only 4 ... 20 mA)
Fig. 29: Current output active with/without HART protocol (4 ... 20 mA)
Contact output
R
B
*
42
+U
G00244
41
R
B
*
U
CE
I
CE
I
E
0 V
24 V DC
Note
Horn and alarm light are shown only
as examples. Other suitable devices
such as bells, sirens, buzzers, etc.,
can also be used.
Contact output:
selectable in software
Function:
Passive
"closed" 0 V
≤
U
CEL
≤
2 V, 2 mA
≤
I
CEL
≤
220 mA
"open" 16 V
≤
U
CEH
≤
30 V, 0 mA
≤
I
CEH
≤
2 mA
Terminals: 41, 42
Fig. 30: Contact output for system monitoring, Max.-Min. alarm for empty tube or forward/reverse signal
Contact input
G00245
+ 16 ... 30 V DC
0 V
82
81
R
i
I
E
Contact input:
selectable in software
Function:
Passive
"On" 16 V
≤
U
KL
≤
30 V
"Off" 0 V
≤
U
KL
≤
2 V
Ri = 2 k
Ω
Terminals: 81, 82
Fig. 31: Contact input for external totalizer reset and external zero return