Communication
41
* 6-digit register addressing (400001) is used instead of 5-digit
register addressing (40001) to describe register map. See section
for additional information.
** Register addresses of the 32-bit parameters cannot be
accessed by using 5-digit register numbers.
400060
DATA IN 7
400061
DATA IN 8
400062
DATA IN 9
400063
DATA IN 10
400064
DATA IN 11
400065
DATA IN 12
400101-409999
Drive Parameter Access (16-bit)
Register Address = 100 x Group + Index
Example for Drive Parameter 3.18
100 x 3 + 18 = 400318
Register addressing of the 32-bit parameters (not
supported with ACS350):
200 x Group + 2 x Index
Example for Drive Parameter 1.27
200 x 1 + 2 x 27 = 420254
Register Address*, **
Register Data (16-bit)