14
Table 1. FSCA-01 configuration parameters - group A *
* Actual parameter group number depends on the drive type. Eg,
group A equals to parameter group 51 in ACS350 and ACSM1.
Par. no.
Parameter name
Alternative settings
Default setting
1
FBA TYPE
(Read-only)
RS-485
2
PROTOCOL/
PROFILE
Modbus:
(0) ABB Drives Classic
(1) ABB Drives Enhanced
(2) Transparent 16-bit
(3) Transparent 32-bit
Modbus:
(0) ABB Drives
Classic
3
STATION ID
1…247
1
4
BAUD RATE
(0) 9.6 kbit/s
(1) 19.2 kbit/s
(2) 38.4 kbit/s
(3) 57.6 kbit/s
(4) 115.2 kbit/s
(0) 9.6 kbit/s
5
PARITY
(0) 8 NONE 1
(1) 8 NONE 2
(2) 8 EVEN 1
(3) 8 ODD 1
(0) 8 NONE 1
6
MODBUS TIMEOUT
0…65535
0
7
TIMEOUT MODE
(0) NONE
(1) ANY MESSAGE
(2) CONTROL WRITE
0
8
OK MESSAGES
0…65535
9
CRC ERRORS
0…65535
10
UART ERRORS
0…65535
11… 26
Reserved
Summary of Contents for FSCA-01