![ABB Foundation LD 810HSE Ex Quick Installation Manual Download Page 32](http://html.mh-extra.com/html/abb/foundation-ld-810hse-ex/foundation-ld-810hse-ex_quick-installation-manual_2718032.webp)
32 Quick Installation Guide LD 810HSE Ex |
2PAA118721
Vertical Installation Position Maximum number
of fieldbus chan-
nels used
Maximum
fieldbus
voltage
Minimum
distance
Maximum per-
missible ambient
temperature T
A
4
32 V DC
0 mm
40 °C
2
24 V DC
0 mm
50 °C
4
32 V DC 17.5 mm
55 °C
2
24 V DC 17.5 mm
60 °C
The maximum permissible ambient
temperature values are also valid for a 180°
rotated installation position.