Connection procedure
Connect the network cables to connectors [X1] and [X2] on the module.
1.
Connect the cable from the master to the left port [X1].
2.
In the line topology, if there are more slave devices in the same line, connect the next slave
device to the right port [X2].
Start-up
To control the drive with the adapter module, set at least the basic parameters listed in the table
below. For full parameter descriptions, refer to the adapter module’s user manual or to the drive’s
firmware manual.
Basic parameter settings
To take the settings into use, validate and refresh the parameters with parameter
51.27 FBA par
refresh
.
Further information
Index
Name
Value
20.01
Ext1 commands
Fieldbus A
22.11
Speed ref1 source
FBA A ref 1
28.11
Frequency ref1 source FBA A ref 1
50.01
FBA A enable
Enable (or select the option slot in which the module is installed). This
activates the communication module. The HOST LED becomes green.
50.02
FBA A comm loss func Fault
51.02
Profile
The CANopen device profile (CiA 402) is the default value.
See the latest version of
FEPL-02 Ethernet POWERLINK adapter
module user's manual (3AUA0000123527 [English])
in ABB library
).
For more information on ABB fieldbus options and protocols,
see the fieldbus communications web page
new.abb.com/drives/connectivity/fieldbus-connectivity
).
page