Connection procedure

Connect the network cables to connectors [X1] and [X2] on the module.

1.

Connect the cable from the master to the left port [X1].

2.

In the line topology, if there are more slave devices in the same line, connect the next slave 
device to the right port [X2].

Start-up

To control the drive with the adapter module, set at least the basic parameters listed in the table 
below. For full parameter descriptions, refer to the adapter module’s user manual or to the drive’s 

firmware manual.

Basic parameter settings

To take the settings into use, validate and refresh the parameters with parameter 

51.27 FBA par 

refresh

.

Further information

Index

Name

Value

20.01

Ext1 commands

Fieldbus A

22.11

Speed ref1 source

FBA A ref 1

28.11

Frequency ref1 source FBA A ref 1

50.01

FBA A enable

Enable (or select the option slot in which the module is installed). This 

activates the communication module. The HOST LED becomes green.

50.02

FBA A comm loss func Fault

51.02

Profile

The CANopen device profile (CiA 402) is the default value.

See the latest version of 

FEPL-02 Ethernet POWERLINK adapter 

module user's manual (3AUA0000123527 [English]) 

in ABB library 

(

www.abb.com/drives/documents

).

For more information on ABB fieldbus options and protocols, 

see the fieldbus communications web page 

(

new.abb.com/drives/connectivity/fieldbus-connectivity

).