Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters.
See the appropriate drive manual.
Basic parameter settings
Protocol-specific parameter settings
T
o take the settings into use, validate and refresh the parameters with parameter
51.27 FBA par refresh
.
Further information
Index
Name
Value
20.01
Ext1 commands
Fieldbus A
22.11
Speed ref1 source
FBA A ref 1
28.11
Frequency ref1 source
FBA A ref 1
50.01
FBA A enable
Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.
50.02
FBA A comm loss func
Fault
PROFINET IO
Ethernet/IP
Index
Name
Value
Index
Name
Value
51.02
Protocol/Profile
PNIO ABB Pro
51.02
Protocol/Profile
EIP AC/DC
51.04
IP configuration
Static IP
51.04
IP configuration
Set the IP address
according your network
configuration.
51.05...08
IP address
0.0.0.0
51.05...08
IP address
51.09
Subnet CIDR
0
51.09
Subnet CIDR
52.01
FBA A data in1
SW 16bit
51.23
Speed scale
128
52.02
FBA A data in2
Act 16bit
53.01
FBA A data out1
CW 16bit
Modbus/TCP
53.02
FBA A data out2
Ref1 16bit
Index
Name
Value
51.02
Protocol/Profile
Modbus/TCP
51.04
IP configuration
Set the IP address
according your network
configuration.
Connectivity configuration
51.05...08
IP address
To access the configuration web page:
1. Open a web browser and type the IP address of the
adapter module in the address field.
2. Log in with a user name (
admin
) and a password (The
last six digits of the MAC address of the adapter module,
in upper case letters, without hyphens. Eg, if MAC ID is
00-1C-01-00-2F-73, the password is
002F73
).
51.09
Subnet CIDR
See the latest version of
FENA-01/-11/-21 Ethernet adapter
module user’s manual
www.abb.com/drives/documents
)
.
new.abb.com/drives/connectivity/fieldbus-connectivity
).