32 Technical data
Isolation areas
Digital inputs (XDI1:1…2, XDI2:3…4, XDI3:5…6)
•
Connector pitch 5 mm, wire size max. 2.5 mm
2
•
Torque: 0.5 N·m
•
Input voltages: 24…250 V DC or 110…230 V AC
•
Logic levels (DC): “0” < 5 V, “1” > 15 V
•
Logic levels (AC) 110…230 V ±10%: “0” < 5 V
rms
, “1” > 20 V
rms
•
Input currents: 10 mA at 24 V DC, 3 mA at 230 V AC
•
Filtering times, selectable for all channels:
10 ms (default),1 ms
•
Inputs isolated from each other, the relay outputs, power
supply and ground (earth)
•
Varistor protected (250 V)
•
Insulation strength: > 4 kV
Symbol
Description
Basic insulation (IEC 61800-5-1:2007)
Summary of Contents for FDIO-01