The display is connected to the protector via the
supplied 1 m cable (2 m or 4 m cable optional - contact
ABB Furse).
The remote display drilling template can be found at the
back of these instructions.
Connecting leads up to 50 cm (20 inches) can be used when:
(i) two sets of 6 mm
2
cables are used (ie two sets of live,
neutral and earth conductors). Each set of conductors is
tightly bound together, using Ty-Raps
®
, tape or spiral
wrap.
This should be done for the entire length of the cable or
as far as is possible. The two sets of bound conductors
should be separated in their routeing. Ideally a distance
of 10 cm (4 inches) should be maintained between the
two sets of conductors as far as possible.
See Figure 11
.
3/13
| Installation instructions for mains wire-in protectors
Figure 11:
For connecting leads of up to 50 cm use two
sets of conductors (L1, L2, L3, N, ). Each
set of conductors has been tightly bound
and separated in their routeing.