1/12 Installation |
Instruction Bulletin EOHU364/5/6JK/RK/S/SS, 1SCC340038M1401 / A
Installation
Wiring
Wiring
Connect the power wires to the switch terminals and connect
the ground wire to the ground terminal block inside the
enclosure. Reference the National Electric Code and all local
codes for appropriate wire size and grounding requirements.
See chapter Cabling.
All cables must have 167 °F / 75 °C minimum rating.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See general safety instructions on page 1/2 before proceeding.
Failure to follow these instructions will result in death or serious injury.
Switch terminals are not intended to support the weight of the
cables, so installer must provide adequate cable support. To
avoid placing a strain on the line and load terminals, bend the
cable carefully. Undue strain may cause terminal distortion and
adversely affect the performance of the switch.
Safety
switch
size [A]
Line and load side
terminal lugs
Ground bus
Wire range [kcmil / mm
2
]
200
2 - 600 / 35 - 300
#14 - 2 / 2.5 - 35
400
(2) #2 - 600 / 2 × 35 - 300
#6 - 250 / 10 - 120
600
(2) #2 - 600 / 2 × 35 - 300
#6 - 250 / 10 - 120
Wire strip length L [in / mm]
200
1.10 - 1.18 / 28 - 30
0.39 - 0.47 / 10 - 11.9
400
1.34 - 1.42 / 34 - 36
0.91 - 0.99 / 23 - 25
600
1.34 - 1.42 / 34 - 36
0.91 - 0.99 / 23 - 25
Wire tightening torque
[lbs.in]
[Nm]
[lbs.in]
[Nm]
200
375
41.8
50
5.6
400
500
55.7
275
31.1
600
500
55.7
275
31.1