1
Instruction Bulletin EOHU364/5/6JK/RK/S/SS, 1SCC340038M1401 / A
| Cabling 1/7
Cabling
Heavy duty non-fusible safety switches
Cabling / Non-fusible safety switches
Cable entry/exit locations:
Top entry-bottom exit.
Cable entry/exit through top/bottom endwalls maximize the
cable bending area. All cable entry/exit must be in accordance
with the National Electrical Code and all other local codes. Use
3/8 (for 200 A) or 1/2 (for 400 A and 600 A) Hex key / wrench.
See chapter Wiring.
WARNING
To avoid hazard of electric shock, turn off and lock out all power
sources before installing or performing maintenance on this equipment.
Non-fusible safety switch catalog number
EOHU364_
EOHU365_
EOHU366_
AMPS
200
400
600
Line side terminal lugs
Terminal lug
OZXA-400
OZXA-800
OZXA-800
Torque: wire tightening for Cu and Al cables
lbs.in
375
500
500
Nm
41.8 55.7
55.7
Lug mounting torque
lbs.in
228
480
480
Nm
25.4
53.5
53.5
Wire range
kcmil
#2 - 600
(2) #2 - 600
(2) #2 - 600
mm
2
35 - 300
2 × 35 - 300
2 × 35 - 300
Load side terminal lugs
Terminal lug
OZXA-400
OZXA-800
OZXA-800
Torque: wire tightening for Cu and Al cables
lbs.in
375
500
500
Nm
41.8 55.7
55.7
Lug mounting torque
lbs.in
228
480
480
Nm
25.4
53.5
53.5
Wire range
kcmil
#2 - 600
(2) #2 - 600
(2) #2 - 600
mm
2
35 - 300
2 × 35 - 300
2 × 35 - 300
Ground bus (2 lugs)
Screwdriver
Slot
5/16” Hex
5/16” Hex
Ground bus catalog number
OZXG1
OZXG2
OZXG2
Torque: wire tightening for Cu and Al cables
lbs.in
50
275
275
Nm
5.6
31.1
31.1
Maximum stud mounting torque
lbs.in
72
72
72
Nm
8.1
8.1
8.1
Wire range
AWG
#14 - 2
#6 - 250 kcmil
#6 - 250 kcmil
mm
2
2.5 - 35
10 - 120
10 - 120
Summary of Contents for EOHU Series