![ABB EAS822 Operating Instruction Download Page 39](http://html.mh-extra.com/html/abb/eas822/eas822_operating-instruction_3045242039.webp)
EAS822, EBS852, EBS862
ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D
39
Fuses
Type
Fuse
Installation location
Design
Rated current of fuse
at 115 V AC
at 230 V AC
EBS852
External fuse
External
–
16 A, time-lag
16 A, time-lag
Mains fuse
Connection area
G-fuse cartridge
5 × 20 mm
12.5 A, time-lag
10 A, time-lag
Brake fuse
Power supply board
G-fuse cartridge
5 × 20 mm
0.315 A, medium time-lag 0.315 A, medium time-lag
DC link fuse
Power supply board
G-fuse cartridge
6.3 × 32 mm
10 A, super fast-acting
10 A, super fast-acting
Fuse for binary outputs (3x)
Connection area
G-fuse cartridge
5 × 20 mm
–
0.2 A, medium time-lag
EBS862
External fuse*
External
Safety fuse / thermal
circuit breaker
–
35 A / 16 A
Brake fuse
Power supply board
G-fuse cartridge
5 × 20 mm
–
0.315 A, medium time-lag
DC link fuse
Power supply board
G-fuse cartridge
6.3 × 32 mm
–
15 A, super fast-acting
Fuse for binary outputs (3x)
Connection area
G-fuse cartridge
5 × 20 mm
–
0.2 A, medium time-lag
* The 35 A safety fuse and the 16 A thermal circuit breaker are included in the scope of delivery. The conductor cross-section between the fuse and the electronic
system must be at least 2.5 mm
2
(14 AWG).
Change from one to two columns