EAS822, EBS852, EBS862
ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D
29
Connection of the power and signal cable on the actuator
Note
A metal divider separates the two cable areas inside the
universal plug.
To exclude mutual interference from electromagnetic fields, the
signal and power cables in the connector housing must be
routed and connected separately.
1
Connector housing
2
Shielding (clamps)
3
Plug insert HAN 24E
4
Signal cable
5
Separator
6
Power cable
Figure 19: Universal plug on the actuator
NOTICE
Damage due to improper installation!
When connecting the shielding, make sure that the individual
wires of the cables are not damaged.
• When installing the connector housing, make sure that the
sealing ring is not damaged.
• If the sealing ring is damaged, contact the manufacturer.
1.
Remove the connector housing.
2.
Cut the cable sheath to the required length.
3.
Separate the cable shield and pull it back over the outer
sheath
4.
Push the cable through the cable gland and fasten it with the
clamp.
5.
Make sure that the cable shield is in contact with the clamp
and the connector housing.
6.
Connect the cable (see
Electronic unit EAS822 (Contrac) /
EBS852 (Contrac)
on page 21).
7.
Check the cable connections for tight fit and fasten the cable
gland.
8.
Insert the connector housing and re-tighten.