Section 5
1MRS240173-IB B
4x Registers
46
REF615R
DPU2000R Modbus Point List Mitigation Manual
Table 20:
Mitigation of Modbus mapping for fault records block
DPU2000R
register addr.
DPU 2000R
description
Scale
REF615R
register
addr.
Scale
IEC 61850 path
Comments on REF615R
Modbus points mapping
41409
Data Control
1=First record;
2=Next record;
3=Oldest
Unreported record
1
41409
1
Data Control 1=First record;
2=Next record; 3=Oldest
Unreported record
41410
Fault type element
1
41410
1
LD0.FLTMSTA1.ProFcn.stVal
Protection function, see table
7.1 from “Feeder Protection
and Control REF615R Modbus
Point List Manual”
(1MRS240052-IB)
41411
Active set and recl.
Seq.
1
41463
1
LD0.FLTMSTA1.ActSG.stVal
Active setting group
41464
1
LD0.FLTMSTA1.ShotPntr.stVal
Auto reclosing shot pointer
value Au
41412
Fault number
1
41412
1
Fault number after device
powers up, it does not count
fault records saved before
power up.
41413
Year
1
41413
1
Year
41414
Month
1
41414
1
Month
41415
Day
1
41415
1
Day
41416
Hours
1
41416
1
Hours
41417
Minutes
1
41417
1
Minutes
41418
Seconds
1
41418
1
Seconds
41419
Hundredths of
Seconds
1
41419
1
Hundredths of Seconds
41420
Ia (Scale at
register 41424)
1
41420
100
LD0.FLTMSTA1.AmpsA.mag.f
reading per unit value by
default
41421
Ib (Scale at
register 41424)
1
41421
100
LD0.FLTMSTA1.AmpsB.mag.f
reading per unit value by
default
41422
Ic (Scale at register
41424)
1
41422
100
LD0.FLTMSTA1.AmpsC.mag.f
reading per unit value by
default
41423
In (Scale at
register 41424)
1
41423
100
LD0.FLTMSTA1.AmpsN.mag.f
reading per unit value by
default
41424
Current ( I ) Scale x
1
41424
1
100 by default
41425
Ia Angle
1
N/A in REF615R
41426
Ib Angle
1
N/A in REF615R
41427
Ic Angle
1
N/A in REF615R
41428
In Angle
1
N/A in REF615R
41429
Zero Seq I (Mag)
1
41430
Pos Seq I (Mag)
1
41430
100
LD0.FLTMSTA1.AmpsPsSeq.mag.f
41431
Neg Seq I (Mag)
1
41431
100
LD0.FLTMSTA1.AmpsNgSeq.mag.f
41432
Zero Seq I (Ang)
1
N/A in REF615R
41433
Pos Seq I (Ang)
1
N/A in REF615R
41434
Neg Seq I (Ang)
1
N/A in REF615R