3.3
Multi cabinet configuration
The DPA UPScale ST S2 may be paralleled to increase the power capacity up to 400 kW in steps of
10 or 20 kW. A maximum of 20 modules can be paralleled. The following system configurations are
available:
DPA UPScale S2
ST40
ST60
ST80
ST120
ST200
Number of modules
per frame
2
3
4
6
10
Parallel frames
per system
4
4
4
3
2
Max number of
modules per system
8
12
16
18
20
Max. total system
capacity w/o redundancy
160 kW
240 kW
320 kW
360 kW
400 kW
The multiple cabinet systems are delivered with:
UPS A
UPS B
UPS C
System graphical display
•
-
-
Parallel interface
•
•
•
Parallel cable
•
•
-
The start-up of a multiple cabinet systems is an operation which can be performed by a service
engineer form the manufacturer or by a service engineer from an agent certified by the manufacturer.
Please refer to the service manual to perform this operation.
Fig 3.3-1: Multi cabinet configuration