131
Service
3ADW000195R0501 DCS800 Service Manual e e
Set type code
The type code - TypeCode (97.01) - is preset in the factory and is write protected.
It identifies the drives current-, voltage-, temperature measurement and its
quadrant type. The type code can be changed as whole or individually.
To change the type code as whole follow the instructions below:
un-protect the type code by means of ServiceMode (99.06) = SetTypeCode
set TypeCode (97.01) = S01-0020-04 to S02-5200-05 (details, see table
below)
The drive’s basic type code: DCS800-AAX-YYYY-ZZB
Product family:
DCS800
= S0 Modules
= R0 Rebuild system
= E0 Panel solution
Type: AA
= A0 Enclosed converter
= 1
single bridge (2-Q)
Bridge type:
X
= 2
2 anti parallel bridges (4-Q)
Module type:
YYYY
=
converter type current
= 04
230 VAC - 400 VAC
= 05
230 VAC - 525 VAC
= 06
270 VAC - 600 VAC
= 07
315 VAC - 700 VAC
= 08
360 VAC - 800 VAC
= 10
450 VAC - 990 VAC
Rated AC Voltage:
ZZ
= 12
540 VAC - 1200 VAC
= -
Standard D1 - D6
= L
Left side D7
= R
Right side D7
Power connection:
B
= a
Second thyristor type D5, D6
Attention:
When using D1, D2, D3 or D4 modules the current and voltage range of the type
code setting is limited to max 1000 ADC and max 600 VAC.
the change of the type code is immediately taken over and ServiceMode
(99.06) is automatically set back to NormalMode
the new values can be seen in group 4
ConvNomCur (4.05),
ConvNomVolt (4.04),
MaxBridgeTemp (4.17) and
QuadrantType (4.15)