18
7.1
Coils
Coil No.
Variable Label
Read/Write
Limits/Values
1
Process Variable Fail State
R
1 = Failed
3
A/D Converter Fail State
R
1 = Failed
6
Alarm State 1
R
1 = Active
7
Alarm Indicator 1
R
1 = On
8
Alarm State 2
R
1 = Active
9
Alarm Indicator 2
R
1 = On
10
Alarm State 3
R
1 = Active
11
Alarm Indicator 3
R
1 = On
14
Digital Input State
R
1 = On
15
Digital Output State
R
1 = On
16
Relay 1 State
R
1 = On
17
Relay 2 State
R
1 = On
21
Global Maths Reset
W
1 = Reset
22
Maximum Values Reset
W
1 = Reset
23
Minimum Values Reset
W
1 = Reset
24
Average Values Reset
W
1 = Reset
7.2
Registers
7.2.1 Analog Inputs
Register
Variable Label
Read/Write
Limits/Values
1 + 2
Process Variable Input
R
–9999 to 99999
3
PV Decimal Places
R
0 to 4
4 + 5
Specific Gravity
R/W
–999.9 to 9999.9
5 + 6
Volume
R
–999.9 to 9999.9
7
ADDRESSABLE PARAMETERS
Summary of Contents for DATUM L150