14
…5
MODBUS FUNCTIONS
5.4
Preset Single Register – Function Code 06
5.4.1
Preset Single Register Query
The Preset Single Register Query modifies the contents of a holding register.
Note. Function codes 05, 06 and 16 are the only messages that are
recognized as valid for broadcast.
Example – write the value 500 to holding register address 25 (proportional
band 1 – heat) in slave 01.
Note. To write to a register, its offset address (one less than the register
number) must be used, e.g. to write to register 25, the offset address 24 (18H)
is transmitted.
Register Register
Data
Data
Error
Address
Function
Offset
Offset
Value
Value
Check
(CRC-16)
High
Low
High
Low
Field
01
06
00
18
01
F4
09
DA
5.4.2
Preset Single Register Response
The response to a Preset Single Register Response requests is to retransmit the
query message after the register has been altered.
Example
Register Register
Data
Data
Error
Address
Function
Offset
Offset
Value
Value
Check
(CRC-16)
High
Low
High
Low
Field
01
06
00
18
01
F4
09
DA