4
CP1484, CP1485, CP1486, CP3484, CP3485, CP3486
Data sheet V 1.00
CPU and X2X Link supply
Input voltage
24 VDC (-15 % / +20 %)
Input current
Max. 2.2 A
Reverse polarity protection
Yes
Fuse
Integrated, cannot be exchanged
X2X Link supply output
Rated output power
7.0 W
Parallel operation
Yes
1)
Redundant operation of
X2X Link supply
Yes
I/O supply input
Input voltage
24 VDC (-15 % / +20 %)
Fuse
Recommended pre-fusing max. 10 A slow-blow
I/O supply output
Rated output voltage
24 VDC
Allowable contact load
10.0 A
General supply
Status indicators
Overload, operating status, module status
Diagnostics
Module run error
Overload
Yes, with status LED and software status
Yes, with status LED and software status
Electrical isolation
X2X bus supply
I/O supply
Yes
No
General information
Status indicators
CPU function, overtemperature, Ethernet, ETHERNET Powerlink, CompactFlash, battery
Diagnostics
CPU function
Overtemperature
Ethernet
ETHERNET Powerlink
CompactFlash
Battery
Fans
Yes, with status LED
Yes, with status LED
Yes, with status LED
Yes, with status LED
Yes, with status LED
Yes, with status LED and software status
Yes, with software status
Visual Components capable
Yes
ACOPOS™ capable
Yes
Cooling
Fan-free
Fan-free with derating (see
operational conditions)
Exchangeable fans for entire
temperature range
Fan is monitored
Product ID
CP1484
CP3484
CP1485
CP3485
CP1486
CP3486
Table 2: X20 CPUs - technical data (cont.)