5) A dialog box is displayed for configuring the runtime system version. The runtime system
version is already preselected by the user's project settings. Using the drop-down menu, the
runtime system versions stored in the project can be selected. Clicking on the
Browse
button
allows the selected runtime system version to be loaded from the hard drive or from the CD.
Pressing
Next >
opens a pop-up window, which allows the user to select whether the
modules should be downloaded with SYSTEM ROM target memory using the following
runtime system download. Otherwise, modules can also be downloaded using a later
application download.
Pressing
Next >
brings the user to a control box where the current settings are displayed.
6) The download procedure is started by pressing
Finish
. Download progress is shown in a
message window.
7) To operate the runtime system, the operating mode switch must be turned to 4 when the
download procedure is completed. Reset the CPU or turn off and then on again if necessary.
8) The PLC is now ready for use.
Runtime system update
When updating the runtime system (online runtime system update), the following procedure
must be carried out:
1) An online runtime system update is only possible if a valid operating system is located on the
CompactFlash.
2) Establish an online connection between the programming device (PC or Industrial PC) and
the CPU. An online runtime update is now possible using the interfaces configured as an
online interface.
The runtime system update can be completed using either a serial online connection
(INA2000 protocol), a CAN network, or an ETHERNET network, depending on the system
configuration.
3) Start B&R Automation Studio™ programming environment.
4) Start the update procedure by calling the
Services
command from the
Project
menu. Select
Transfer Operating System...
from the menu shown. Now follow the instructions from B&R
Automation Studio™.
Information:
The User Flash is cleared.