Electromagnetic compatibility
Interference immunity to
IEC/EN 61000-6-2
electrostatic discharge
IEC/EN 61000-4-2 Level 4 (8 kV / 15 kV)
radiated, radio-frequency, electromagnetic field
IEC/EN 61000-4-3 Level 3 (10 V/m)
electrical fast transient/burst
IEC/EN 61000-4-4 input circuit: Level 4 (4 kV)
output circuit: Level 3 (2 kV)
surge
IEC/EN 61000-4-5 input circuit: L-L Level 3 (2 kV) / L-PE Level 4 (4 kV)
output circuit: Level 1 (0.5 kV)
conducted disturbances, induced by radio-
IEC/EN 61000-4-6 Level 3 (10 V, 150 kHz - 80 MHz)
frequency fields
voltage dips, short interruptions and voltage
variations
IEC/EN 61000-4-11 Class 3
Interference emission
IEC/EN 61000-6-3
high-frequency radiated
IEC/CISPR 22, EN 55022 Class B
high-frequency conducted
IEC/CISPR 22, EN 55022 Class B
limits for harmonic current emissions
IEC/EN 61000-3-2 Class A