Technical data
Data at T
a
= 25 °C, U
in
= 230 V AC and rated values, unless otherwise indicated
Input circuit – Supply circuit
L, N
Rated input voltage U
in
switch position 115 V 100-120 V AC
switch position 230 V 220-240 V AC
Input voltage range
switch position 115 V 85-132 V AC
switch position 230 V 184-264 V AC
Frequency range AC
47-63 Hz
Typical input current
switch position 115 V 2.0 A
switch position 230 V 0.9 A
Typical power consumption
94 W
Inrush current limiting / I²t (cold start)
< 20 A (132 V AC) / approx. 1.5 A²/s
< 38 A (264 V AC) / approx. 1.8 A²/s
Discharge current towards PE
< 3.5 mA
Power failure buffering time
at 115 V AC min. 35 ms
at 230 V AC min. 40 ms
Transient overvoltage protection
varistor
Internal input fuse
2.5 A slow acting / 250 V AC
External fusing (not necessary, but recommended)
circuit breaker with C characteristic min. 6 A,
or alternatively 10 A with B characteristic
Power Factor Correction (PFC)
at 115 V AC 0.58
at 230 V AC 0.53
Indication of operational states
Output voltage
AS-I OK LED green
IR addressing mode
IR ADDRESSING ON LED red
Output circuit
+, -
Rated output power
85 W
Rated output voltage
30.5 V DC
Tolerance of the output voltage
± 3 %
Rated output current I
r
T
a
≤ 60 °C 2.8 A
Derating of the output current
60 °C < T
a
≤ 70 °C 2.5 % / °C
Control time
< 2 ms
Starting time after applying the supply voltage
max. 400 ms
Rise time
max. 100 ms
Residual ripple
BW = 500 kHz typ. < 50 mV
pp
Switching peaks
BW = 20 MHz typ. < 100 mV
pp
Output circuit – No-load, overload and short-circuit behaviour
Characteristic curve of output
U/I characteristic curve
Short-circuit protection
continuous short-circuit stability
Short-circuit behavior
continuation with output power limiting
Current limiting at short circuit
min / max 3.2 A / 4.6 A
Overload protection
output power limiting
No-load protection
continuous no-load stability