10.4 OUTPUT CHARACTERISTICS
Output characteristics
UPS frame
values
UPS module
values
Unit
Power, rated:
500
100 kW
AC power distribution system: TN-S, TN-C, TN-C-S, TT
available phases
3
neutral available
yes
Voltage (steady state, r.m.s.), rated:
3x380/220V+N
3x400/230V+N
3x415/240V+N
VAC
variation in normal mode / battery mode
± 1.5 / ± 1.5 %
Total harmonic distortion (THDu), 100% load, normal mode:
linear
< 2.0
%
non-linear (according to IEC 62040-3)
< 4.0
Total harmonic distortion, 100 % load, battery mode:
linear
< 2.0
%
non-linear (according to IEC 62040-3)
< 4.0
Voltage unbalance and phase displacement, 100 % load unbalance
0 °
Voltage transient and recovery time, 100% step load:
linear
± 4 %
non-linear (according to IEC 62040-3)
± 4 %
transfer normal mode --> battery mode
0 %
Frequency (steady-state), rated:
50/60 Hz
variation in normal mode (frq. Synchronized with mains)
± 2 / ± 4
%
variation in battery mode (free-running)
± 0.1
Max synch phase error (referred to a 360° cycle)
<2 °
Max slew-rate
1 Hz/s
Nominal current (In), r.m.s. rated:
725
145 A
overload on inverter
0.5 @ 150% load,
5 @ 125% load,
20 @ 110% load
min
fault clearing capability normal mode and battery mode for 100ms
1711 (2.36xIn)
348 (2.4xIn) A
Load power factor, rated
1
displacement (permissible lead-lag range)
(all range) 0 %, s
AC / AC efficiency in normal mode, linear load:
100% load
95.6
%
75% load
96.0
50% load
96.1
25% load
95.8
Eco-mode efficiency, linear load
≥ 99 %
Crest – Factor (Load supported)
3:1
Static bypass
Type: automatic, static switch in each module
transfer time: inverter
bypass / bypass
inverter / in eco-mode
<1 / <5 / <6 ms
rated current
800
160 A
fault clearing capability (bypass mode) for 20 ms
10xIn
10xIn A
overload current on bypass mode (< 25°C)
continuously @ 110% load
min
Maintenance bypass: optional on the frame
Bypass protection fuse or circuit breaker rating
5x160 A, gL fuse