The value of the voltage property on the voltage level object is used for the voltage level
based busbar coloring mode.
Configuring the powered state for incoming feeder and generator
1.
Select the IFL or GEN object in the SLD editor.
2.
Right-click it, and select Configure Powered Rule from the menu.
There are three different rules for detecting the powered state. Configure at least one of
the following three rules so that the busbar coloring works correctly.
•
A measurement value must be greater than the configured value.
•
A data object value is equal to the configured value.
•
A data object value is unequal to the configured value.
If the result of all configured rules is true, the object is considered as powered by the
busbar coloring logic.
sldPoweredRule.png
Figure 3.5.1-7 The Powered rule dialog
Voltage level SLD
To create a voltage level SLD:
1.
Drag the bays to correct locations in the SLD (name of the selected bay can be seen
in the property grid).
28
1MRS756740
COM600 series, Version 4.1
HMI Configuration Manual